環氧接地銅(tong)箔網(wang)絡概述:
環氧自流平(ping)防(fang)(fang)靜(jing)電(dian)(dian)地(di)(di)面的(de)施(shi)工內(nei)容中(zhong),包含有銅(tong)箔構成的(de)網絡,這(zhe)些金屬(shu)網絡彼此形成電(dian)(dian)氣通路,用于(yu)防(fang)(fang)靜(jing)電(dian)(dian)地(di)(di)面的(de)靜(jing)電(dian)(dian)傳導。作為電(dian)(dian)氣設計配合,應該(gai)將防(fang)(fang)靜(jing)電(dian)(dian)地(di)(di)面所在的(de)建筑柱(zhu)(zhu)上,適當預留接(jie)(jie)地(di)(di)端子盒。在地(di)(di)面施(shi)工完畢后,將防(fang)(fang)靜(jing)電(dian)(dian)地(di)(di)面內(nei)的(de)金屬(shu)線與(yu)該(gai)接(jie)(jie)地(di)(di)端子盒相連。另外,該(gai)接(jie)(jie)地(di)(di)端子在土建施(shi)工過程中(zhong)須通過柱(zhu)(zhu)內(nei)主(zhu)筋與(yu)接(jie)(jie)地(di)(di)極焊接(jie)(jie)連通,以使(shi)靜(jing)電(dian)(dian)通過接(jie)(jie)地(di)(di)端子沿柱(zhu)(zhu)內(nei)主(zhu)筋流向(xiang)地(di)(di)極。防(fang)(fang)靜(jing)電(dian)(dian)接(jie)(jie)地(di)(di)電(dian)(dian)阻(zu)一般要(yao)求不大于(yu)10歐姆。
1、工藝流程
2、施工方法
清理(li)地(di)面,尋(xun)找中(zhong)心線(xian)。首(shou)先將(jiang)地(di)面浮灰(hui)清除干凈,然后用量具找出(chu)房間(jian)的(de)中(zhong)心位置,畫出(chu)中(zhong)心十(shi)字(zi)線(xian),要(yao)求十(shi)字(zi)線(xian)垂(chui)直等分。
在地面底涂(tu)施(shi)(shi)工(gong)完成涂(tu)料充(chong)分干(gan)透(tou)后(hou),進(jin)行二(er)次打磨處理并(bing)進(jin)行地面的清潔維(wei)護(hu),施(shi)(shi)工(gong)區域(yu)用警示帶等標示性的材料進(jin)行隔(ge)離,以防止(zhi)人(ren)員誤闖(chuang)入施(shi)(shi)工(gong)區域(yu)。做好上述準備后(hou)就可以進(jin)行導(dao)電膠層的施(shi)(shi)工(gong),導(dao)電層施(shi)(shi)工(gong)利用刮板進(jin)行涂(tu)裝作(zuo)業(ye),要求(qiu)導(dao)電層涂(tu)料厚度均勻。
鋪設銅(tong)箔(bo)網絡:在(zai)銅(tong)箔(bo)涂上少許導電(dian)(dian)膠,從中心位(wei)置開始相鄰(lin)鋪于地面,縱向2.4米到3.6米鋪設--根銅(tong)箔(bo)。銅(tong)箔(bo)必須(xu)有(you)兩處以上沿墻壁用6平方的(de)軟編織(zhi)帶引(yin)出約(yue)700mm,引(yin)出的(de)編織(zhi)帶與(yu)等電(dian)(dian)位(wei)端子箱相連,并選(xuan)用PVC 線槽進行保護,等電(dian)(dian)位(wei)端子箱內裝40*4的(de)銅(tong)排(pai),預(yu)留10個M8螺栓。
銅箔敷設完成(cheng)后,進(jin)行中涂的施(shi)工,然(ran)后是面層,整個(ge)過程按序進(jin)行。