環(huan)氧接地銅(tong)箔網(wang)絡概(gai)述:
環(huan)氧自流(liu)平防靜電(dian)(dian)(dian)地(di)(di)面的(de)(de)施(shi)工內(nei)(nei)(nei)容中(zhong),包含有(you)銅箔構成的(de)(de)網(wang)絡,這些金(jin)屬網(wang)絡彼此形成電(dian)(dian)(dian)氣通(tong)路,用(yong)于(yu)防靜電(dian)(dian)(dian)地(di)(di)面的(de)(de)靜電(dian)(dian)(dian)傳導。作為電(dian)(dian)(dian)氣設(she)計配合,應該(gai)將防靜電(dian)(dian)(dian)地(di)(di)面所在的(de)(de)建(jian)筑(zhu)柱上,適當預留接(jie)地(di)(di)端(duan)子(zi)(zi)盒。在地(di)(di)面施(shi)工完(wan)畢后,將防靜電(dian)(dian)(dian)地(di)(di)面內(nei)(nei)(nei)的(de)(de)金(jin)屬線(xian)與該(gai)接(jie)地(di)(di)端(duan)子(zi)(zi)盒相連。另外,該(gai)接(jie)地(di)(di)端(duan)子(zi)(zi)在土建(jian)施(shi)工過(guo)程中(zhong)須通(tong)過(guo)柱內(nei)(nei)(nei)主(zhu)筋與接(jie)地(di)(di)極焊(han)接(jie)連通(tong),以使(shi)靜電(dian)(dian)(dian)通(tong)過(guo)接(jie)地(di)(di)端(duan)子(zi)(zi)沿柱內(nei)(nei)(nei)主(zhu)筋流(liu)向地(di)(di)極。防靜電(dian)(dian)(dian)接(jie)地(di)(di)電(dian)(dian)(dian)阻一般要求不大于(yu)10歐(ou)姆。
1、工藝流程
2、施工方法
清理地面,尋找中心線。首先(xian)將地面浮灰清除干凈,然后用量具找出房間的中心位置,畫出中心十字線,要(yao)求十字線垂直等分。
在地面(mian)底涂施(shi)(shi)工完成涂料充分干透后,進(jin)行(xing)(xing)二次打磨(mo)處理(li)并(bing)進(jin)行(xing)(xing)地面(mian)的清潔維護,施(shi)(shi)工區域用警(jing)示帶等(deng)標示性的材料進(jin)行(xing)(xing)隔(ge)離,以防止人(ren)員誤(wu)闖入施(shi)(shi)工區域。做好上述準備后就可以進(jin)行(xing)(xing)導電(dian)膠層的施(shi)(shi)工,導電(dian)層施(shi)(shi)工利(li)用刮板進(jin)行(xing)(xing)涂裝作業,要求導電(dian)層涂料厚度(du)均(jun)勻。
鋪設銅(tong)箔(bo)(bo)網絡:在(zai)銅(tong)箔(bo)(bo)涂上(shang)少許導電(dian)膠(jiao),從中心位(wei)置開始(shi)相(xiang)鄰鋪于地面(mian),縱向2.4米(mi)到3.6米(mi)鋪設--根銅(tong)箔(bo)(bo)。銅(tong)箔(bo)(bo)必須有兩處以上(shang)沿(yan)墻壁(bi)用6平方的軟(ruan)編織帶引出約700mm,引出的編織帶與等(deng)電(dian)位(wei)端子箱相(xiang)連(lian),并選用PVC 線槽進行(xing)保護,等(deng)電(dian)位(wei)端子箱內裝(zhuang)40*4的銅(tong)排,預(yu)留(liu)10個M8螺栓。
銅箔敷設完成后(hou),進行中涂(tu)的施工,然后(hou)是面層,整個過(guo)程按序進行。