1.使用環氧防靜電中涂漆:主漆和固化劑按比例混合后加適量填料(如石英粉、滑石粉)攪拌均勻;
2.用(yong)批(pi)刀批(pi)括1-2遍,重點是填補地面(mian)的(de)坑洞缺(que)陷處;
3.待固化后,打(da)磨批(pi)刀痕等(deng)缺(que)陷處,用(yong)吸塵器、擰干的濕毛巾等(deng)清理干凈。
環氧(yang)導電批土(tu)層(ceng)驗收指(zhi)標包括(kuo):
A、表面電(dian)(dian)阻(阻值符合(he)在(zai)1.0×106Ω—1.0×109Ω)一在(zai)一給定的(de)通電(dian)(dian)時間(jian)(jian)之后,施加于材(cai)料表面上(shang)的(de)標準(zhun)電(dian)(dian)極(ji)(ji)之間(jian)(jian)的(de)直流電(dian)(dian)壓對(dui)于電(dian)(dian)極(ji)(ji)之間(jian)(jian)的(de)電(dian)(dian)流的(de)比值,在(zai)電(dian)(dian)極(ji)(ji)上(shang)可(ke)能的(de)極(ji)(ji)化(hua)現(xian)象忽略不(bu)計。
B、系統電(dian)(dian)阻(阻值符合在5.0×104Ω—1.0×109Ω)一(yi)被測(ce)物(wu)體測(ce)試(shi)表面與被測(ce)物(wu)體接(jie)地點之(zhi)間電(dian)(dian)阻總和。
C、系(xi)統接(jie)(jie)地(di)(di)(di)(di)電(dian)(dian)(dian)阻(zu)(zu)(阻(zu)(zu)值≤10Ω)一。電(dian)(dian)(dian)流由接(jie)(jie)地(di)(di)(di)(di)系(xi)統流入大(da)(da)地(di)(di)(di)(di)再經大(da)(da)地(di)(di)(di)(di)流向另(ling)一接(jie)(jie)地(di)(di)(di)(di)體或(huo)向遠(yuan)(yuan)處(chu)擴(kuo)散所遇到的電(dian)(dian)(dian)阻(zu)(zu),它包括接(jie)(jie)地(di)(di)(di)(di)線和接(jie)(jie)地(di)(di)(di)(di)體本身的電(dian)(dian)(dian)阻(zu)(zu)、接(jie)(jie)地(di)(di)(di)(di)體與大(da)(da)地(di)(di)(di)(di)的電(dian)(dian)(dian)阻(zu)(zu)之間的接(jie)(jie)觸電(dian)(dian)(dian)阻(zu)(zu)以及(ji)兩接(jie)(jie)地(di)(di)(di)(di)體之間大(da)(da)地(di)(di)(di)(di)的電(dian)(dian)(dian)阻(zu)(zu)或(huo)接(jie)(jie)地(di)(di)(di)(di)體到無限大(da)(da)遠(yuan)(yuan)處(chu)的大(da)(da)地(di)(di)(di)(di)電(dian)(dian)(dian)阻(zu)(zu)。