1.使用環氧防靜電中涂漆:主漆和固化劑按比例混合后加適量填料(如石英粉、滑石粉)攪拌均勻;
2.用批刀批括(kuo)1-2遍,重點是(shi)填補地面的坑洞缺陷處;
3.待(dai)固(gu)化后,打(da)磨批刀痕(hen)等缺陷處,用(yong)吸塵器、擰干的濕(shi)毛巾等清理干凈。
環氧導電批(pi)土(tu)層驗收(shou)指標包括:
A、表面(mian)電(dian)阻(阻值(zhi)符(fu)合在(zai)1.0×106Ω—1.0×109Ω)一在(zai)一給定(ding)的通電(dian)時間(jian)(jian)之(zhi)后(hou),施加于材料表面(mian)上的標準(zhun)電(dian)極之(zhi)間(jian)(jian)的直(zhi)流電(dian)壓(ya)對于電(dian)極之(zhi)間(jian)(jian)的電(dian)流的比值(zhi),在(zai)電(dian)極上可(ke)能的極化(hua)現象忽略不計。
B、系統電阻(zu)(阻(zu)值符合在5.0×104Ω—1.0×109Ω)一被測(ce)物體(ti)測(ce)試(shi)表面與被測(ce)物體(ti)接地(di)點(dian)之(zhi)間(jian)電阻(zu)總和。
C、系統接(jie)(jie)地(di)(di)(di)電(dian)(dian)(dian)阻(zu)(zu)(阻(zu)(zu)值≤10Ω)一(yi)。電(dian)(dian)(dian)流(liu)(liu)由接(jie)(jie)地(di)(di)(di)系統流(liu)(liu)入大(da)地(di)(di)(di)再經大(da)地(di)(di)(di)流(liu)(liu)向另一(yi)接(jie)(jie)地(di)(di)(di)體或向遠處擴散所(suo)遇到的(de)電(dian)(dian)(dian)阻(zu)(zu),它包括接(jie)(jie)地(di)(di)(di)線和接(jie)(jie)地(di)(di)(di)體本身(shen)的(de)電(dian)(dian)(dian)阻(zu)(zu)、接(jie)(jie)地(di)(di)(di)體與大(da)地(di)(di)(di)的(de)電(dian)(dian)(dian)阻(zu)(zu)之(zhi)間的(de)接(jie)(jie)觸電(dian)(dian)(dian)阻(zu)(zu)以及兩接(jie)(jie)地(di)(di)(di)體之(zhi)間大(da)地(di)(di)(di)的(de)電(dian)(dian)(dian)阻(zu)(zu)或接(jie)(jie)地(di)(di)(di)體到無(wu)限大(da)遠處的(de)大(da)地(di)(di)(di)電(dian)(dian)(dian)阻(zu)(zu)。