1.使用環氧防靜電中涂漆:主漆和固化劑按比例混合后加適量填料(如石英粉、滑石粉)攪拌均勻;
2.用批刀批括(kuo)1-2遍,重點(dian)是填補地面的坑(keng)洞缺陷處(chu);
3.待固化后,打(da)磨(mo)批(pi)刀痕(hen)等缺陷處,用吸塵器、擰干的濕毛巾等清理干凈。
環氧導電批土層驗收(shou)指標包括:
A、表面電(dian)阻(阻值(zhi)符合在1.0×106Ω—1.0×109Ω)一在一給(gei)定的通電(dian)時間之(zhi)后(hou),施加于材料表面上的標準電(dian)極(ji)之(zhi)間的直流電(dian)壓(ya)對于電(dian)極(ji)之(zhi)間的電(dian)流的比(bi)值(zhi),在電(dian)極(ji)上可能的極(ji)化現象(xiang)忽略不(bu)計。
B、系統電(dian)阻(阻值符(fu)合在5.0×104Ω—1.0×109Ω)一被測物(wu)體測試表面與被測物(wu)體接地點之間電(dian)阻總(zong)和。
C、系(xi)統(tong)接(jie)地(di)(di)(di)(di)電(dian)阻(zu)(zu)(zu)(阻(zu)(zu)(zu)值≤10Ω)一。電(dian)流由接(jie)地(di)(di)(di)(di)系(xi)統(tong)流入大(da)(da)(da)地(di)(di)(di)(di)再經(jing)大(da)(da)(da)地(di)(di)(di)(di)流向(xiang)另一接(jie)地(di)(di)(di)(di)體或向(xiang)遠(yuan)處擴散所遇到(dao)的電(dian)阻(zu)(zu)(zu),它包(bao)括(kuo)接(jie)地(di)(di)(di)(di)線和接(jie)地(di)(di)(di)(di)體本身的電(dian)阻(zu)(zu)(zu)、接(jie)地(di)(di)(di)(di)體與大(da)(da)(da)地(di)(di)(di)(di)的電(dian)阻(zu)(zu)(zu)之(zhi)間(jian)的接(jie)觸電(dian)阻(zu)(zu)(zu)以及兩(liang)接(jie)地(di)(di)(di)(di)體之(zhi)間(jian)大(da)(da)(da)地(di)(di)(di)(di)的電(dian)阻(zu)(zu)(zu)或接(jie)地(di)(di)(di)(di)體到(dao)無限(xian)大(da)(da)(da)遠(yuan)處的大(da)(da)(da)地(di)(di)(di)(di)電(dian)阻(zu)(zu)(zu)。